1 / 3
Backflow Preventer

BFPX โ€“ Back Flow Preventer

Debug ยท supplier source (internal only)

Specifications

Confirmed at quote
Size Range
DN15โ€“DN250
Pressure Class
PN10 / PN16
Standards
EN 1717, EN 12729
End connection
Threaded (DN15โ€“DN50) / Flanged (DN65+)

Available sizes

Standard DN sizes covered by this product. Confirmed at quote.

Available pressure classes

Pressure classes this product is rated to.

Configure your variant(manually adjust box on the right if you require a different spec)

Size
Pressure
End connection

Materials

Body

Pressure-temperature rating

Maximum working pressure at each temperature, per pressure class.

ClassTemperatureMax pressure
PN10-10ยฐC10 bar
PN1080ยฐC10 bar
PN16-10ยฐC16 bar
PN1680ยฐC16 bar
Dimensions per size(11 sizes)
SizeLOD_PN10OK_PN10OD_PN16OK_PN16Weight
DN50230 mm165 mm125 mmโ€”โ€”โ€”
DN65236 mm185 mm145 mmโ€”โ€”โ€”
DN80276 mm200 mm160 mmโ€”โ€”โ€”
DN100298 mm220 mm180 mmโ€”โ€”โ€”
DN125303 mm250 mm210 mmโ€”โ€”โ€”
DN150364 mm285 mm240 mmโ€”โ€”โ€”
DN200470 mm340 mm295 mmโ€”โ€”โ€”
DN250530 mm395 mm350 mm405 mm355 mmโ€”
DN300580 mm445 mm400 mm460 mm410 mmโ€”
DN350690 mm505 mm460 mm520 mm470 mmโ€”
DN400770 mm565 mm515 mm580 mm525 mmโ€”

Approvals

WRASISO 9001

Features

  • The BFPX provides reduced pressure zone (RPZ) backflow prevention to EN 1717 for fluid category 4 and 5 hazards
  • The assembly comprises two independent check valves with a monitored relief valve in the zone between them
  • If either check valve fails, the relief valve opens to atmosphere, preventing contaminated downstream water from siphoning back into the potable supply
  • Mandatory for connections to industrial processes, irrigation and commercial premises under current European water regulations

Description

RPZ and DCV assemblies to EN 1717 for potable protection. The BFPX provides reduced pressure zone (RPZ) backflow prevention to EN 1717 for fluid category 4 and 5 hazards. The assembly comprises two independent check valves with a monitored relief valve in the zone between them. If either check valve fails, the relief valve opens to atmosphere, preventing contaminated downstream water from siphoning back into the potable supply. Mandatory for connections to industrial processes, irrigation and commercial premises under current European water regulations.

Smart find

Searches our product catalogue using your spec. Drop a PDF โ€” or multiple PDFs at once โ€” paste a description or a part number and we'll find the closest matches for each. Anything we can't match goes to your RFQ as a custom enquiry for our team to source.
BFPX โ€“ Back Flow Preventer | Euro Flow Control