1 / 4
Control Valve
Part of the A900 modular system

A204 Pressure Reducing Valve with Flow Limiter

Debug · supplier source (internal only)

Specifications

Confirmed at quote
Size Range
DN50–DN400
Pressure Class
PN16
Standards
EN 1074-5
End connection
Flanged PN16

Available sizes

Standard DN sizes covered by this product. Confirmed at quote.

Configure your variant(manually adjust box on the right if you require a different spec)

Size
Pressure
End connection

Materials

Body
Diaphragm

Pressure-temperature rating

Maximum working pressure at each temperature, per pressure class.

ClassTemperatureMax pressure
PN10-10°C10 bar
PN1080°C10 bar
PN16-10°C16 bar
PN1680°C16 bar
PN25-10°C25 bar
PN2580°C25 bar
Dimensions per size(16 sizes)
SizeLHOD_PN10OD_PN16OD_PN25OK_PN10OK_PN16OK_PN25OB_PN10OB_PN16OB_PN25Weight
DN50230 mm177 mm165 mm165 mm165 mm125 mm125 mm125 mm99 mm99 mm99 mm
DN65290 mm202 mm185 mm185 mm185 mm145 mm145 mm145 mm118 mm118 mm118 mm
DN80310 mm219 mm200 mm200 mm200 mm160 mm160 mm160 mm132 mm132 mm132 mm
DN100350 mm243 mm220 mm220 mm235 mm180 mm180 mm190 mm156 mm156 mm156 mm
DN125400 mm243 mm250 mm250 mm270 mm210 mm210 mm220 mm156 mm156 mm156 mm
DN150480 mm333 mm285 mm285 mm300 mm240 mm240 mm250 mm211 mm211 mm211 mm
DN200600 mm428 mm340 mm340 mm360 mm295 mm295 mm310 mm266 mm266 mm274 mm
DN250730 mm478 mm405 mm405 mm425 mm350 mm355 mm370 mm319 mm319 mm330 mm
DN300850 mm538 mm460 mm460 mm485 mm400 mm410 mm430 mm370 mm370 mm389 mm
DN350980 mm550 mm520 mm520 mm555 mm460 mm470 mm490 mm429 mm429 mm448 mm
DN4001100 mm710 mm580 mm580 mm620 mm515 mm525 mm550 mm480 mm480 mm503 mm
DN4501200 mm720 mm640 mm640 mm670 mm565 mm585 mm600 mm530 mm548 mm548 mm
DN5001250 mm822 mm715 mm715 mm730 mm620 mm650 mm660 mm582 mm609 mm609 mm
DN6001450 mm885 mm840 mm840 mm845 mm725 mm770 mm770 mm682 mm720 mm720 mm
DN7001650 mm910 mm910 mm910 mm960 mm840 mm840 mm875 mm682 mm720 mm720 mm
DN8001850 mm1260 mm1025 mm1025 mm1085 mm950 mm950 mm990 mm901 mm901 mm928 mm

Approvals

WRASISO 9001

Features

  • The A204 combines downstream pressure reduction with a flow limiter in a single valve
  • The dual pilot arrangement simultaneously limits the maximum flow rate and reduces downstream pressure to the set point
  • When demand exceeds the flow limit, the flow control pilot takes authority regardless of the PRV set point
  • Used at district supply points where both pressure and demand must be controlled

Description

The A204 combines downstream pressure reducing and flow limiting in a single A900 valve body, using a P200 reducing pilot and P400 flow control pilot. Under normal demand the P200 pilot controls downstream pressure; when demand exceeds the flow limit the P400 pilot takes authority regardless of the PRV set point. An Alpine orifice plate provides the differential pressure signal for the flow pilot. Used at district supply points where both pressure and maximum demand must be controlled.

Smart find

Searches our product catalogue using your spec. Drop a PDF — or multiple PDFs at once — paste a description or a part number and we'll find the closest matches for each. Anything we can't match goes to your RFQ as a custom enquiry for our team to source.

A900 configurations

View full A900 system →
This product is part of the A900 modular system. All configurations share the same hydraulically operated body: the control function is set by the pilot valve(s) attached. An existing A900 body in the field can be reconfigured for a different duty simply by swapping the pilot, without replacing the body.

Pilot assembly & accessories

Compatible accessories

Related Control Valves

A204 Pressure Reducing Valve with Flow Limiter | Euro Flow Control