1 / 4
Control Valve

P26M Pressure Management Valve (Time Based)

Debug Β· supplier source (internal only)

Specifications

Confirmed at quote
Size Range
DN50–DN400
Pressure Class
PN16
Standards
EN 1074-5
End connection
Flanged PN16

Available sizes

Standard DN sizes covered by this product. Confirmed at quote.

Configure your variant(manually adjust box on the right if you require a different spec)

Size
Pressure
End connection

Materials

Body

Pressure-temperature rating

Maximum working pressure at each temperature, per pressure class.

ClassTemperatureMax pressure
PN10-10Β°C10 bar
PN1080Β°C10 bar
PN16-10Β°C16 bar
PN1680Β°C16 bar
PN25-10Β°C25 bar
PN2580Β°C25 bar
Dimensions per size(16 sizes)
SizeLHOD_PN10OD_PN16OD_PN25OK_PN10OK_PN16OK_PN25OB_PN10OB_PN16OB_PN25Weight
DN50230 mm177 mm165 mm165 mm165 mm125 mm125 mm125 mm99 mm99 mm99 mmβ€”
DN65290 mm202 mm185 mm185 mm185 mm145 mm145 mm145 mm118 mm118 mm118 mmβ€”
DN80310 mm219 mm200 mm200 mm200 mm160 mm160 mm160 mm132 mm132 mm132 mmβ€”
DN100350 mm243 mm220 mm220 mm235 mm180 mm180 mm190 mm156 mm156 mm156 mmβ€”
DN125400 mm243 mm250 mm250 mm270 mm210 mm210 mm220 mm156 mm156 mm156 mmβ€”
DN150480 mm333 mm285 mm285 mm300 mm240 mm240 mm250 mm211 mm211 mm211 mmβ€”
DN200600 mm428 mm340 mm340 mm360 mm295 mm295 mm310 mm266 mm266 mm274 mmβ€”
DN250730 mm478 mm405 mm405 mm425 mm350 mm355 mm370 mm319 mm319 mm330 mmβ€”
DN300850 mm538 mm460 mm460 mm485 mm400 mm410 mm430 mm370 mm370 mm389 mmβ€”
DN350980 mm550 mm520 mm520 mm555 mm460 mm470 mm490 mm429 mm429 mm448 mmβ€”
DN4001100 mm710 mm580 mm580 mm620 mm515 mm525 mm550 mm480 mm480 mm503 mmβ€”
DN4501200 mm720 mm640 mm640 mm670 mm565 mm585 mm600 mm530 mm548 mm548 mmβ€”
DN5001250 mm822 mm715 mm715 mm730 mm620 mm650 mm660 mm582 mm609 mm609 mmβ€”
DN6001450 mm885 mm840 mm840 mm845 mm725 mm770 mm770 mm682 mm720 mm720 mmβ€”
DN7001650 mm910 mm910 mm910 mm960 mm840 mm840 mm875 mm682 mm720 mm720 mmβ€”
DN8001850 mm1260 mm1025 mm1025 mm1085 mm950 mm950 mm990 mm901 mm901 mm928 mmβ€”

Approvals

WRASISO 9001

Features

  • The P26M provides time-based pressure management, automatically reducing network pressure during low-demand periods (typically overnight) and restoring pressure for daytime demand
  • Lower overnight pressures significantly reduce background leakage and burst frequency
  • The time-based actuator requires no external power or SCADA connection, making it a fully hydraulic, self-contained solution

Description

Time-based pressure reduction to minimise leakage. The P26M provides time-based pressure management, automatically reducing network pressure during low-demand periods (typically overnight) and restoring pressure for daytime demand. Lower overnight pressures significantly reduce background leakage and burst frequency. The time-based actuator requires no external power or SCADA connection, making it a fully hydraulic, self-contained solution.

Smart find

Searches our product catalogue using your spec. Drop a PDF β€” or multiple PDFs at once β€” paste a description or a part number and we'll find the closest matches for each. Anything we can't match goes to your RFQ as a custom enquiry for our team to source.

Related Control Valves

P26M Pressure Management Valve (Time Based) | Euro Flow Control